HYDRAULIC CONCENTRATE CONTROL VALVES (07 HCV)
Product Line
| Model 07 HCV | 1” – 3” |
Description
Designed for use with either a foam bladder tank or an inline balanced pressure proportioning system. The valve will automatically open the line supplying foam concentrate to a ratio flow controller. It does not require electrical power to operate, only water pressure from the system that has been activated.
Six valve choice. Minimum operating pressure is 2.4 bar (35 psi) with maximum pressure of 8.27 bar (120 psi). Maximum overload pressure is 10 bar (150 psi).
General Specification
| Valve Body | 316SS Stainless Steel |
| Actuator Body | Corrosion resistant |