FIXED-FOAM-WATER-HYDRANT-STATIONS

FIXED FOAM / WATER HYDRANT STATIONS

Product Line

Model 02 FWHS11 113 litres tank with 200 lpm eductor/nozzle
Model 02 FWHR12 113 litres tank with 400 lpm eductor/nozzle
Model 02 FWHR13 227 litres tank with 200 lpm eductor/nozzle
Model 02 FWHR14 227 litres tank with 400 lpm eductor/nozzle

Description

Fixed Foam-Water Hydrant Stations are ideal first aid fire fighting apparatus that require only a pressurised water supply for operation. Suitable for protection against hydrocarbon fuel fires. The Hydrant Station consists of essential components like foam concentrate tank, variable inline eductor, hose and foam making branchpipe. These components are housed in a robust weatherproof housing.

The performance is solely governed by the foam making branchpipe being used. The container is suitable for storing all type of foam concentrates.

Inlet connection: 2” BSPT union. Outlet : 21⁄2” female instantaneous coupling (BS336) with plastic blank cap and chain. Alternative fittings are available on request.

General Specification:

Typical Disk Specification:
Housing Material Mild steel epoxy coated.
Option: 304SS or 316SS stainless steel
Tank Capacity 113 or 227 litres (30 or 60 gallons)
Tank Material 304 SS or 316SS stainless steel
Hose Size 2 1⁄2” diameter x 30 metres with 2 1⁄2″ instantaneous light alloy couplings
Hose Specification Type 3 textile woven reinforced synthetic with Nitrile/PVC outer cover
Prepiped Eductor 227 lpm or 360 lpm (60 or 95 gpm)
Eductor Material Brass
Nozzle Type Air-aspirating pattern. Inlet, 2 1⁄2” male instantaneous coupling
Nozzle Material Stainless Steel or Aluminum Alloy
Shutoff Valve Type Ball, Brass, 2” threads

Download Catalogue (pdf)